TTD – Transmitting Terminal Device - is intended for:
– controlling two own alarm loops and processing system events by built-in indicators, 3 outputs (Relay 1, Relay 2, OC) and transmitting signals to RTD via radio;
– receiving signals from CP connected through LIN interface and transferring them to receiver (RTD) via radio.
– retransmitting of the signals.
TTD – Transmitting Terminal Device - is intended for:
– controlling two own alarm loops and processing system events by built-in indicators, 3 outputs (Relay 1, Relay 2, OC) and transmitting signals to RTD via radio;
– receiving signals from CP connected through LIN interface and transferring them to receiver (RTD) via radio.
– retransmitting of the signals.
Features
- Wireless coverage range with included whip antenna up to 3400 m (in line of sight);
- Wireless coverage range with external 3 dB antenna up to 12400 m (in line of sight);
- 2-level retransmission via another TTDs;
- 3 modes: standalone, extended and radio extender mode;
- standalone mode: TTD controls 2x built-in hardwire zones;
- extended mode: using Astra-712/x control panel as an extender up to 8 hardwired zones;
- radio extender mode: repeater mode the status of transmitter Zones translated to receiver relays;
- radio supervision;
- tampering control;
- configuring using software ARM-Y or jumpers;
- whip antenna included;
- external antennas supported.
Name | Description |
---|---|
Operating frequency | 433 MHz |
Number of frequency channels | 16 |
Transmitter power | 10/30/100 mW |
Wireless coverage range: - standard whip antenna - external 3 dB antenna (power 10/30 mW) - external 3 dB antenna on transmitter and receiver (power 100 mW) |
2500/3400 m 4500/8700 m 12400 m |
Hardwired zones specification: | |
hardwire zones voltage | 10.5 to 15 V |
short circuit current | 20 mA |
current for powering active hardwired detectors | 3 mA |
Integration time of hardwired zones: | |
intrusion zone | 500 msec |
fire alarm zone | 300 msec |
Zone resistance: | |
Norm | 3 to 5 kOhm |
Alarm | 0 to 3 or more than 5 kOhm |
Fire alarm | 1.5 to 3 or 5 to 12 kOhm |
Failure | 0 to 1.5 or more than 12 kOhm |
Zone resistance (fire alarm double event mode): | |
Norm | 3 to 5 kOhm |
Fire alarm | 0 to 1.5 or to 5 to 12 kOhm |
Fire danger | 1.5 to 3 kOhm |
Failure | more than 12 kOhm |
Supply voltage | 10.5 - 15 V |
Max current consumption | 180 mA |
Boot time of receiver | 8 sec |
Max load voltage of built-in relay | 100 V |
Max load current of built-in relay | 100 mA |
Max load current of open collector output | 100 mA |
Max load voltage of open collector output | 70 V |
Interface line LIN length (at R <100 Ohm, C < 0.033 uF) | 200 m |
Temperature range | -10 to +50 °С |
Relative air humidity | up to 95% at +35 °С |
IP protection | IP41 |